Euchner AS-i Safety Output Relay with four standard inputs Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
12
Subject to reasonable modifications due to technical advances Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
AS-i Safety Output Relay with four standard inputs
Product Description
4.2 Technical Data
Inputs 3 standard inputs + 1 EDM
Outputs 1 relay
3 A, 24 V, DC-13 or 3 A, 230 V, AC-15 respectively
AS-i profile S.7.A.E
ID1 Code 5
hex
(default), user changeable
External device monitoring (EDM) Supplied from AS-i, about 24 V, about 10 mA
Displays
3 LEDs yellow (I 1, I 2, I 3) Status input I1, I2, I3
1 LED yellow (1.Y1) Status EDM input 1.Y1
LED green (PWR) AS-i power supply
LED red (FAULT) AS-i error LED
LED yellow (OUT) See table for flashing LED pattern "Device colors"
LED red (ALARM) PLC signals alarm
Operational current < 200 mA
Supply power for sensors 90 mA
Operational current AS-i (30 V
DC
)
Over-voltage category 3 for operating voltage 300 V
AC
acc. to VDE 0110 part 1
Voltage isolation 6kV
Utilized standards EN 954-1 Cat 4
IEC 61 508 SIL 3
EN 13849-1:2006/PLe Cat 4
EN IEC 6 2061 SIL 3
Housing DIN rail mountable housing
Ambient operating temperature 0°C ... +55 °C
Storage temperature -25°C ... +85 °C
Dimensions
(length/ width/ height in mm)
114 / 22,5 / 99
Protection category according to
DINEN60529
Housing IP20
Device Colors
Value Color Description State change LED "Out"
0 green Output on on
1 green flashing
2 yellow Error lock Auxiliary signal 2 1 Hz
3 yellow flashing
4 red Output off off
5 red flashing Waiting for error unlock signal Auxiliary signal 1 8 Hz
6 gray Internal error, for instance "fatal
error"
Only through turning power "on"
on the device
all LEDs are
flashing
7 green/yellow Output released but not turned on Switched "on" by setting O1 off