AS-i Safety Output Relay with four standard inputs
Product Description
Subject to reasonable modifications due to technical advances Id.-No.: 103573 Issue date - 28.5.2009 EUCHNER GmbH + Co. KG
15
Kohlhammerstraße 16 • D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 • Fax. +49/711/753316
4.5 Operating interface
4.6 Indicators
Switch to select the operational mode:
PRG
Safety relevant AS-i address can be programmed
Secure operation not possible.
RUN
Secure operation possible, non-safety relevant AS-i address can be
programmed.
Addressing jack (ADDR)
Indicators
Display Meaning
PWR off No supply power
green 1 Hz flashing Operational power on, safety relevant AS-i address and/or
AS-i AB address is “0”
green (on) Supply power on
Fault off AS-i communication OK
red (on) No data exchange with the AB slave
Out off Output Relay switched off
green 1 Hz flashing Error lock state, waiting for start signal, after transmission
of start signal Output Relay switches on
green 8 Hz flashing The device is in an un-lockable error state. The device
resumes regular operation after the Monitor sent the sig-
nal “error unlock”.
green (on) Output Relay switched on
Alarm off AS-i output bit A0 not set
red (on) AS-i output bit A0 set
I1, I2, I3, 1.Y1 off Corresponding input is not on
yellow
cyclic flashing
Switch set to PRG
yellow (on) Corresponding input is on
I 1I 3
1.Y1I
2
I
–
I
1
1.13
ASI
+
I
+
I
2
1.14
ASI
–
I
+
I
3
1.23
NC
I
+
1.Y1
1.24
NC
ADDR
RUN PRG
FAULT ALARM
PWR
OUT