Operating Instructions Safety Switch CES-AP-C01-CH
8
Mounting
Important!
Ì From the assured switch-off distance S
ar
, the safety outputs are safely shut
down.
Ì When mounting several safety switches, observe the stipulated minimum
distance to avoid mutual interference.
min. 80mm
Ì If the actuator is installed flush, the switching distance changes as a function
of the installation depth and the safety guard material.
Operating
distance
Actuator
Operating
distance
Actuator
Flush mounting
Surface mounting
Note the following points:
Ì Actuator and safety switch must be easily accessible for inspection and re-
placement.
Ì The switching operation must only be triggered by the specific actuator desig-
nated for this purpose. For permissible combinations please see the table of
possible combinations on page 4.
Ì Actuator and safety switch must be fitted so that
Ì the front faces are at the minimum switch-on distance 0.8 x S
ao
or closer
when the safety guard is closed (see section Operating distances). A mini-
mum distance dependent on the actuator must be maintained for a side ap-
proach direction: - for CES-A-BBA 4 mm
- for CES-A-BPA 6 mm
- for CES-A-BRN 12 mm
Ì when the safety guard is open up to the distance S
ar
(assured switch-off dis-
tance), a hazard is excluded.
Ì the actuator is positively mounted on the safety guard, e.g. by using the
safety screws included.
Ì they cannot be removed or tampered with using simple means.
Ì Pay attention to the maximum tightening torque for the read head or safety
switch and actuator mountings of 1 Nm.
Vista de pagina 7