AS-i 3.0 Command Interface Commands of the Command Interface
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
47
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
4.5.7 Set list of projected slaves (SET_LPS and SET_LPS_R6 (6Bh))
The command SET_LPS_R6 (6Bh) differs from the command SET-LPs in:
• no empty byte (3)
• half so long LPS list
With the bit 2
5
is selected if the upper (=1) or lower (=0) part of the LCS is read.
With this call, the list of configured AS-i slaves is transferred for permanent storage
in the EEPROM of the master.
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart).
This command can only be executed in the configuration mode.
Request (if O ≡ 0)
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
129
16
2T 0 circuit
300
16
47A6A5A4A3A2A1A –
……
11 31B 30B 29B 28B 27B 26B 25B 24B
Request (if O ≡ 1)
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
129
16
2T 1 circuit
300
16
4 – 1A 2A 3A 4A 5A 6A 7A
……
11 24B 25B 26B 27B 28B 29B 30B 31B
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
129
16
2T result
Comentarios a estos manuales