AS-i 3.0 Command Interface Command Interface Examples
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
77
No result because toggle bit = 0.
Set the toggle bit:
Master is now in configuration mode.
Result = 0 No error, for other result codes see chapter 4 Commands of the
Command Interface, page 12 "Commands of the Command Interface".
2. Write the actual slave configuration to the master
Response
Byte 1 00
hex
(or old values)
Byte 2 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Request: SET_OP_MODE
Byte 1 0C
hex
(SET_OP_MODE)
Byte 2 80
hex
(T = 1, master 1, single master)
Byte 3 01
hex
(= config mode)
Byte 4 00
hex
……
Byte 12 00
hex
Response
Byte 1 0C
hex
Byte 2 80
hex
(T = 1, result = 0)
Byte 3 00
hex
(or old values)
……
Byte 12 00
hex
(or old values)
Request: STORE_CDI
Byte 1 07
hex
(STORE_CDI)
Byte 2 00
hex
(T = 0, master 1, single master)
Byte 3 00
hex
……
Byte 12 00
hex